How to clear emergency stop alarm/fault (E2800) in liquid cooled units

How to clear emergency stop alarm/fault (E2800) in liquid cooled units

In order to clear the alarm you will need to do the following:

1. Locate the toggle switch, this is located on the side of the unit. (Examples below depicted in red)


2. Turn the switch to the upright position
3. On the same side the switch is located there will be a control panel to the left of it. Open the lid and you will see the picture above. (depicted in red)
4. This will have an error code/ fault of E2800 emergency stop. In order to clear the alarm you will have to put the unit to 'Off' then press enter a few times and this should clear the fault. After should read either 'ready to run' or 'run hours (sequence of numbers)'.
5. Turn unit to auto and should have a green light now and be ready to run when you are in an outage.